Name CVE-2022-31207 First vendor Publication 2022-07-26
Vendor Cve Last vendor Modification 2024-11-21

Security-Database Scoring CVSS v3

Cvss vector : CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Overall CVSS Score 9.8
Base Score 9.8 Environmental Score 9.8
impact SubScore 5.9 Temporal Score 9.8
Exploitabality Sub Score 3.9
 
Attack Vector Network Attack Complexity Low
Privileges Required None User Interaction None
Scope Unchanged Confidentiality Impact High
Integrity Impact High Availability Impact High
Calculate full CVSS 3.0 Vectors scores

Security-Database Scoring CVSS v2

Cvss vector :
Cvss Base Score N/A Attack Range N/A
Cvss Impact Score N/A Attack Complexity N/A
Cvss Expoit Score N/A Authentication N/A
Calculate full CVSS 2.0 Vectors scores

Detail

The Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS (9600/TCP) protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication flaws as reported in FSCT-2022-0057. Control logic is downloaded to PLC volatile memory using the FINS Program Area Read and Program Area Write commands or to non-volatile memory using other commands from where it can be loaded into volatile memory for execution. The logic that is loaded into and executed from the user program area exists in compiled object code form. Upon execution, these object codes are first passed to a dedicated ASIC that determines whether the object code is to be executed by the ASIC or the microprocessor. In the former case, the object code is interpreted by the ASIC whereas in the latter case the object code is passed to the microprocessor for object code interpretation by a ROM interpreter. In the abnormal case where the object code cannot be handled by either, an abnormal condition is triggered and the PLC is halted. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, thus allowing an attacker to manipulate transmitted object code to the PLC and either execute arbitrary object code commands on the ASIC or on the microprocessor interpreter.

Original Source

Url : http://cve.mitre.org/cgi-bin/cvename.cgi?name=CVE-2022-31207

CWE : Common Weakness Enumeration

% Id Name
100 % CWE-347 Improper Verification of Cryptographic Signature

CPE : Common Platform Enumeration

TypeDescriptionCount
Os 1
Os 1
Os 1
Os 1
Os 1
Os 1
Os 1

Sources (Detail)

https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02
https://www.forescout.com/blog/
Source Url

Alert History

If you want to see full details history, please login or register.
0
1
2
3
Date Informations
2024-11-28 14:10:59
  • Multiple Updates
2022-08-04 21:27:34
  • Multiple Updates
2022-07-27 13:27:13
  • Multiple Updates
2022-07-27 05:27:06
  • First insertion