This CPE summary could be partial or incomplete. Please contact us for a detailed listing.

Summary

Detail
Vendor Ge First view 2022-03-23
Product Multilin b90 Firmware Last view 2022-03-23
Version Type Os
Update  
Edition  
Language  
Sofware Edition  
Target Software  
Target Hardware  
Other  

Activity : Overall

COMMON PLATFORM ENUMERATION: Repartition per Version

CPE Name Affected CVE
cpe:2.3:o:ge:multilin_b90_firmware:*:*:*:*:*:*:*:* 6

Related : CVE

  Date Alert Description
9.8 2022-03-23 CVE-2021-27428

GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The weakness is assessed, and mitigation is implemented in firmware Version 8.10.

9.8 2022-03-23 CVE-2021-27426

GE UR IED firmware versions prior to version 8.1x with “Basic†security variant does not allow the disabling of the “Factory Mode,†which is used for servicing the IED by a “Factory†user.

5.3 2022-03-23 CVE-2021-27424

GE UR firmware versions prior to version 8.1x shares MODBUS memory map as part of the communications guide. GE was made aware a “Last-key pressed†MODBUS register can be used to gain unauthorized information.

7.5 2022-03-23 CVE-2021-27422

GE UR firmware versions prior to version 8.1x web server interface is supported on UR over HTTP protocol. It allows sensitive information exposure without authentication.

5.3 2022-03-23 CVE-2021-27420

GE UR firmware versions prior to version 8.1x web server task does not properly handle receipt of unsupported HTTP verbs, resulting in the web server becoming temporarily unresponsive after receiving a series of unsupported HTTP requests. When unresponsive, the web server is inaccessible. By itself, this is not particularly significant as the relay remains effective in all other functionality and communication channels.

6.1 2022-03-23 CVE-2021-27418

GE UR firmware versions prior to version 8.1x supports web interface with read-only access. The device fails to properly validate user input, making it possible to perform cross-site scripting attacks, which may be used to send a malicious script. Also, UR Firmware web server does not perform HTML encoding of user-supplied strings.

CWE : Common Weakness Enumeration

%idName
20% (1) CWE-668 Exposure of Resource to Wrong Sphere
20% (1) CWE-434 Unrestricted Upload of File with Dangerous Type
20% (1) CWE-319 Cleartext Transmission of Sensitive Information
20% (1) CWE-79 Failure to Preserve Web Page Structure ('Cross-site Scripting')
20% (1) CWE-20 Improper Input Validation